Products
5kw-20kw on Grid Wind Turbine Inverter Ce Certificate |
|
Product name:5kw-20kw on Grid Wind Turbine Inverter Ce Certificate |
Item: |
Details: |
Product Description
Product advantages:
1. Using IGBT from Mitsubishi company as the power components
2. Using American ATEMEL company microprocessor as figure controller
3. Perfect protection and warning functions
4. Wind turbine MPPT technology, real-time tracing wind turbine max. output power
5. Disturbance detection technology, anti-island control
6. Circuit frame compact, Max. Efficiency≥94%
7. Outdoor stainless steel shell, fully sealed installation
8. Input voltage within the broad, the maximum reach 1150VDC
9. With RS485/RS232, Ethernet, GPRS (optional) interfaces, remote data collection and surveillance
10. Pure sine wave output, automatic synchronization grid connected, non-polluting to the power grid, no impact
11. Inverting current close-cycle control, power to control and adjustable
12. Big-screen English LCD, perfect display, interface-friendly
5KW-20KW On grid wind turbine inverter technical parameters
Type |
DMWG5KS |
DMWG10KS |
DMWG20KS |
Nominal capacity |
5KW |
10KW |
20KW |
Rated AC output power |
5KW |
10KW |
20KW |
Max. AC output power |
6KW |
11KW |
22KW |
Isolation |
Power frequency transformer |
Max. dc open circuit voltage |
780Vdc |
MPPT range |
300~780Vdc |
Max. DC Input current |
33A |
67A |
100A |
THD of AC current |
<3%(nominal power) |
Power factor |
>0.99 |
Max. Efficiency |
94% |
Euro efficiency |
92% |
Allow the grid voltage range |
310~450Vac ( three phase) |
Nominal AC frequency |
47.5Hz-51.5Hz |
Automatically put into operation |
When the DC input and power grids meet to the requirements, the inverters automated operation |
Auto restart time after cut off |
5min(time adjustment) |
Protection |
Input short voltage, over voltage, connecting contrary, output over current, short circuit, over heat etc. |
Communication interface |
RS485/RS232/GPRS/Ethernet (optional) |
Work environment temperature |
-25ºC~+55ºC |
Relative humidity |
0~95% no condensing |
Applicable altitude |
≤2000m Higher than 2000m rated power should be reduced |
Cooling method |
Controlled forced-air cool |
Noise (1m) |
≤60dB |
Degree of protection |
IP20 |
Size(W*L*H) mm |
500*540*860 |
580*515*1250 |
650*610*1560 |
Weight(kg) |
120 |
150 |
300
|
 |
 |